1.Based on the rated current of the final electric load (motor), it is better that the rated current of the harmonic filter is more than 1.1 times of that of the load current.
2.Look at the rated working current and actual working current of the load, and do not exceed the rated working current of the harmonic filter.
3.Look at the load rate. If the load rate is too low, it will affect the effect of harmonic filter. Please check load rate data when selecting the type.
4.Check the rated working voltage and power frequency of the load equipment to see if it meets the power requirements of the harmonic filter.
5.Attention should be paid to the installation environment of harmonic filters, which meets the requirements of the environment for the use of harmonic filters.
6.It is better to provide the power factor of the load so that suitable capacitors can be installed to achieve the best power factor.

 

SOROTEC Three-phase Balance Active Harmonic Filter(AHF)

Meeting users’ requirements:
– PF=0.99 and THDi < 5%
– Compensation for 2- to 50-order harmonics
– Capacitive and inductive reactive power compensation
– Three-phase unbalance co